Compact light fitting emergency luminaire with battery Explosion-protected Type: 6109/111-0111-180-0111-31-4850-001 Variant: with diffuser 2 x 40° Enclosure material: Thermoset Silicon free: w/o Influence on paint wetting Dimensions (L x W x H): 440 mm x 185 mm x 90 mm Operating voltage AC: 100...240 V ± 10% Operating time: 1.5 / 3h em. lighting op. Battery version: NiCd battery, gas-tight Battery capacity: 2,2 Ah Battery operating voltage: 6 V Application range (zones): 1 , 2 , 21 , 22 Gas explosion protection: II 2 G Ex db eb ib op is IIC T4 Gb Dust explosion protection: II 2 D Ex tb op is IIIC T100 °C Db Min. ambient temperature: -30°C Max. ambient temperature: +60°C IP degree of prot. (IEC 60598): IP66 / IP67 Through wiring: Loop in/loop out wiring Installed terminal strip: PE+N+L1+L2+L3+L''+D1+D2 Max. solid connect. terminals: 6 mm2 Max. fine. strand. conn. term.: 4 mm2 Control interface: DALI Drilled holes: 3 x M25 Accessories: Provided cable entries: 2 x M25 Ø 7 – 17 mm Stopping plug: 2 x M25 x 1.5 Stopping plug material: Polyamide, black For further information, see: r-stahl.com WebCode 6109A
Equipo disponible | Potencia nominal de lámpara | Flujo de lámpara | Eficiencia luminosa | CCT | CRI |
---|---|---|---|---|---|
1 x LED | 11 W | 600 lm | 55 lm/W | 5000 K | 81 |
Tipo de Montaje
Montaje en techo
Forma y medidas
Longitud: 402 mm
Anchura: 190 mm
Altura ajustable: 80 mm
Ajustabilidad
Fijo
Eléctrico
Potencia: 11 W
Balastos: ECG
Control: DALI
Switch integrado: Dentro de la caja
Clases de aislamiento: I
Protección
IP: 66
IK: 08
Clasificaión de zonas explosivas: 1
Otros números operativos
Intervalo de temperatura ambiente: -30...50 °C
Dato fotométrico
ZIP file