Product data sheet

6102/111-0100-150-0111-31-4850-00

287777

Stahl

Compact light fitting Emergency luminaire explosion-protected Type: 6102/111-0100-150-0111-31-4850-00 Variant: With diffuser 2 x 40° Enclosure material: Thermoset Silicone-free content: W/o influence on paint wetting Dimensions (L x W x H): 440 mm x 185 mm x 90 mm Operating voltage AC: 100 to 240 V +- 10% Operating voltage DC: 100 to 250 V +- 10% Application range (zones): 1 , 2 , 21 , 22 Gas explosion protection: II 2 G Ex db eb ib op is IIC Dust explosion protection: II 2 D Ex tb op is IIIC T100 °C Db min. ambient temperature: -40 °C max. ambient temperature: +50 °C IP degree of prot. (IEC 60598): IP66 / IP67 Through wiring: Loop in/loop out Installed terminal strip: PE + N + L1 + L2 + L3 Max solid connection terminals: 6 mm2 Max. fin. str. conn. terminals: 4 mm2 Control interface: without Drilled holes: 3 x M25 Accessories: Provided Cable glands and entries: 2 x M25 Ø 7 – 17 mm Stopping plugs: 2 x M25 x 1.5 Stopping plug material: Polyamide, black For further information, see: r-stahl.com WebCode 6102A 

Available equipment Nominal lamp power Lamp flux Luminous efficacy CCT CRI
1 x LED 9.7 W 600 lm 62 lm/W 5000 K 81
6102/111-0100-150-0111-31-4850-00

6102/111-0100-150-0111-31-4850-00 

Light output 1 

1 x LED 

Mounting mode 

Ceiling mounted

Shape and measurements 

Length: 402 mm

Width: 190 mm

Height: 80 mm

Adjustability 

Fixed

Electric 

System power: 9.7 W

Ballast: ECG

Appliance Class: I

Protection 

IP: 66

IK: 08

Explosion zone suitability: 1

Other operating numbers 

Ambient temperature range: -40...60°C

Photometric data

ZIP file